Search ILC

Products

The LightSync Conditional Occupancy Sensor 8 Input Module (COS8I) allows conditional configurations for each of the 8 inputs, and is designed to power and receive signals from multiple occupancy sensors. Each LightSync input allows for conditional statements related to the occupancy sensor inputs and pilots in the module. ¨AND¨ and ¨OR¨ logic schemes can be configured for each input, allowing users to create overlapping conditionals for multiple occupancy sensor zones within the COS8I module. Each input conditional statement consists of NO/NC closures and LS device pilot status in a 16x16 matrix. The LS device inputs are programmed in the LL panel to control any relay(s), group(s) or preset(s).

  • Programmable conditional occupancy input
  • 8 inputs per module that accept 24V signals
  • Optically isolated inputs to protect electronics
  • Connect multiple sensors to each input
  • Works with major manufacturers 3-wire sensors
  • Installs directly onto output board or remotely
  • Made in the USA
Lighting Applications and CAD
Accessories
Features

General Information:

  • 8 Conditional occupancy sensor inputs per module
  • Provides Power and inputs for occupancy sensors
  • Programmable conditional logic
  • Accepts 2 wiremaintained or momentary closures
  • Connectors are non-screw push-to-connect type
  • Switch closure LED status for each input
  • Optically isolated inputs to protect electronics
  • Installs directly onto output board
  • Remote mounting option for LightSync network
  • Power from 120/277VAC power supply
  • Software logic programming provided
  • Made in the USA
Physical

Specifications

Safeguards:

  • Optically isolated inputs protect electronics

Physical:

  • 2.75¨ W x 3.5¨ H
  • Easy non-screw push-to-connect connectors
  • Digital addressing switches
  • RJ45 connectors for remote mounting option

Remote Mount Physical:

  • Enclosure: 6.50¨ x 9.25¨ x 2.50¨ with screw cover
  • 1/2???nipple for mounting to an electrical box
  • 6??? wire leads provided for high voltage connection
  • Push-to-connect low voltage connections
  • Provided with pre-drilled mounting holes

Electrical:

  • Electronics powered from LightSync data line
  • Sensors powered from 120/277VAC power supply
  • Current: 800mA to power sensors
  • Voltage: 24VDC
  • Current limited circuit

Operating Environment:

  • Location: Interior space
  • Operating Temp.: 0° to 50° C
  • Humidity: 10% - 90% Non-condensing
  • Atmosphere: Non-explosive/corrosive
  • Vibration: Stationary

Certifications and Approvals:

  • FCC Part 15
  • UL