LightLEEDer-2RC Load Room Controller

The LightLEEDer-2RC Room Lighting Controller (LL-2RC) is a 2-relay full feature integrated mini panel with the common features desired for today´s 1 or 2 room control. It has been designed to be used as a stand-alone panel or can be used as an expansion or remote panel from a standard LightLEEDer panel´s local port. As with all of our LightLEEDer panels, it comes with our Reliant40 latching relays which feature a superior four contact design - the first true 40Amp lighting relay. It also has integrated electronics for 2 dimming outputs for controlling 0-10V dimming ballasts, 2 inputs for photocell heads, 4 hardwired inputs, power for occupancy sensors, and a local LightSync port for up to two 6 button data line switches.

  • All products Made in the USA
  • 2 load programmable Room Lighting Controller
  • Stand-alone or Networked
  • LightSync switch capable
  • Built-in photo controller
  • Occupancy sensor interface
  • 0-10V dimming output
  • Suitable for plenum mounting
Features

General Information:

  • Made in the USA
  • 2 load programmable room lighting controller
  • Stand-alone or networked from a LightLEEDer controller
  • Expansion provided from LightLEEDer´s local port
  • Relays are the superior Reliant40 relays
  • Dimming 0-10V outputs integrated for controlling 2 zones
  • 4 inputs for hard wired switches or occupancy sensors
  • Power for occupancy sensors
  • Photocell controller integrated for 2 heads
  • LightSync data line device ready utilizing RJ45 connectors and standard CAT-5 cabling for data line

  • Suitable for plenum mounting

LightLEEDer Expansion Processor (optional):

  • Processor for only controlling LL-2RC, LL4RC, or LL-4X panels
  • Controls up to 16 LL-2RC, LL-4RC, or LL-4X remote panels
  • Provides a sub-net for communications
  • Allows LightSync data line devices and power
  • Provides all standard panel controls
  • Interconnects up with standard panels
  • Combine up to 255 sub-net or standard panels per lighting system
Physical

Specifications

Safeguards:

  • Power surge and spike suppression up to 123 volts on the 24VAC power input
  • Memory retention for firmware and programming up to 200 years and electrostatic discharge to 4kv

Physical:

  • Enclosure: 5¨ x 9¨ x 2¨ galvanized NEMA 1 with screw cover
  • 3/4¨ nipple for mounting to an electrical box
  • 6¨ wire leads provided for high voltage connections
  • Push-to-connect low voltage connections
  • Provided with pre-drilled mounting holes
  • High voltage barriers seperate Class 2 wiring

Integrated Interfaces:

  • 4 inputs for hard wired switches or occupancy sensors
  • Power for occupancy sensors
  • Dimming 0-10V outputs for controlling 2 zones
  • Photocell controller for 2 heads or zones
  • LighSync port for 2 data line switches

Electrical:

  • 120/277 VAC @ .6 amps (120/347 VAC Optional)
  • Inputs: 24 VDC @ 200mA max
  • Dimming: 100 mA sink

Relays:

  • Superior breaker style design
  • 40 amp Reliant40 relays de-rated to 30 amps
  • 30 amp ballast or resistive loads
  • SCCR to 18,000 symmetrical amps

Operating Environment:

  • Location: Interior space
  • Operating Temp.: 0° to 50° C
  • Humidity: 10% - 90% Non-condensing
  • Atmosphere: Non-explosive/corrosive
  • Vibration: Stationary

Certifications and Approvals:

  • UL and CUL listed
  • FCC Part 15
  • Title 24
  • ASHRAE compliant
Accessories