ILC-ESRN Emergency Shunt Relay, 0-10V Override
Model: ILC-ESRN
Our Bypass/Shunt Relays are UL924 Listed and suitable for shunting around wall switches and/or lighting control panel circuits, in order to turn on emergency lighting when normal utility power is lost. Enclosed Relay 20 Amp SPST Automatic Load Control Relay, 120-277 Vac Coil Input, 0-10V Dimmer Override.
Cutsheets
Specifications
- # Relays & Contact Type: One (1) SPST Continuous Duty Coil
- Expected Relay Life: 10 million cycles minimum mechanical
- Operating Temperature: -30 to 140° F
- Operate Time: 18ms
- LED: Green = Normal Power, Red = Emergency Power, Yellow = Load Power
- Dimensions: 4.0˝ x 4.57˝ x 1.80˝ with .50˝ NPT Nipple
- Wires: 16˝, 600V Rated
- Approvals: UL Listed, UL924, C-UL, CE, RoHS
- Housing Rating: UL Accepted for Use in Plenum, NEMA 1
- Gold Flash: No
- Override (Test Switch): Yes
- Humidity Range: 5-95%(noncondensing)
Coil Current:
- Normal Power =24 mA max
- Emergency Power = 118 mA max
Coil Voltage Input:
- Emergency Input: 120-277 Vac (50/60 Hz)
- Normal Input: 120-277 Vac (50/60 Hz)
Contact Ratings:
- 20 Amp Magnetic Ballast @ 277 Vac
- 16 Amp Electronic Ballast @ 277 Vac
- 10 Amp Tungsten @ 120 Vac
Resources