Our Bypass/Shunt Relays are UL924 Listed and suitable for shunting around wall switches and/or lighting control panel circuits, in order to turn on emergency lighting when normal utility power is lost.  Enclosed Relay 20 Amp SPST Automatic Load Control Relay, 120-277 Vac Coil Input, 0-10V Dimmer Override. 

Cutsheets

ILC-ESRN Emergency Shunt Relay

Specifications
  • # Relays & Contact Type:  One (1) SPST Continuous Duty Coil
  • Expected Relay Life:  10 million cycles minimum mechanical
  • Operating Temperature:  -30 to 140° F
  • Operate Time:  18ms
  • LED:  Green = Normal Power, Red = Emergency Power, Yellow = Load Power
  • Dimensions:  4.0˝ x 4.57˝ x 1.80˝ with .50˝ NPT Nipple
  • Wires:  16˝, 600V Rated
  • Approvals:  UL Listed, UL924, C-UL, CE, RoHS 
  • Housing Rating:  UL Accepted for Use in Plenum, NEMA 1
  • Gold Flash:  No
  • Override (Test Switch):  Yes
  • Humidity Range: 5-95%(noncondensing)

Coil Current: 

  • Normal Power =24 mA max
  • Emergency Power = 118 mA max

Coil Voltage Input: 

  • Emergency Input: 120-277 Vac (50/60 Hz)
  • Normal Input: 120-277 Vac (50/60 Hz)

Contact Ratings: 

  • 20 Amp Magnetic Ballast @ 277 Vac
  • 16 Amp Electronic Ballast @ 277 Vac
  • 10 Amp Tungsten @ 120 Vac