LightSync Power Supply Repeater 6 LightSync Power Supply Repeater 6

LightSync Power Supply Repeater 6

Model: LSPSR6-R

The LightSync Digital Power Supply Repeater 6 (LSPSR6) makes branch networking easy. It provides repeated data for 6 outputs supporting both panel and switch communications as well as power for devices. It has a main in and out port for passing network communications through to panels with minimal data loss. This module is ideal for large network data distribution applications.

Cutsheets

LightSync Power Supply Repeater 6

Wiring Diagrams

LightSync Power Supply Repeater (WD0615)

Specifications

Physical:

  • Panel mount module 3.0" x 3.5"
  • Remote mounted in 9.25" x 6.50” x 2.50” standard NEMA-1 enclosure
  • Operates in any position

Electrical:

  • 120/277VAC power supply (120/347VAC Optional)
  • 0.4 Amp at 120VAC

Capacities:

  • Powers up to 20 additional CAT-5 devices at a cumulative distance of 3000 feet across the three branch output pairs combined
  • Main CAT-5 in and out ports for pass through of data
  • Data repeater provide additional 3000 feet end to end per branch output pair
  • Refer to ILC Technical Bulletin #TB 1408 for details on calculating CAT-5 cable run distance

Operating Environment:

  • Location: Interior space
  • Operating Temp.: 0° to 50° C
  • Humidity: 10% - 90% Non-condensing
  • Atmosphere: Non-explosive/corrosive
  • Vibration: Stationary

Certifications and Approvals:

  • FCC Part 15
  • UL CUL
Resources

Technical Bulletins

LightSync Network Cable Run Distance Details (TB1408)

Product Details

LightSync Power Supply Repeater 6 (PD0637)

Features
  • Made in the USA
  • Digital CAT-5 Ready
  • 6 output ports of repeated data
  • Main CAT-5 run in and out ports for direct pass through of data
  • Extend network data length by 3000 feet combined distance end to end for each of the 3 branch output pairs
  • Additional power for up to 20 CAT-5 devices to the 3 branch output runs combined at a cumulative distance of 3000 feet total
  • No programming required