Ceiling Mount Occupancy Sensor, Dual Tech, Line Voltage
The Dual Technology sensor’s combination of Ultrasonic and Passive Infrared technologies offers the most complete sensing equipment available today. MicroSet self-adjusting Dual Technology sensors drastically simplify and reduce a contractor’s installation and adjustment time period.
The MicroSet self-adjusting technology continuously monitors multiple sub-frequencies in the event that if a continuous Doppler shift occurs, such as those created by airflow from an air duct, the sensor will identify the noise as continuous and then block it out of view at a select sub-frequency. It will continue to monitor other sub-frequencies for human motion. This avoids false-activation, while still maintaining the high level of sensitivity that is necessary for sensing minor motion in a changing environment. Separate concurrent time delays for both Passive Infrared and Ultrasonic technologies avoid false activations or deactivations. In Automatic On Mode, the lights turn ON when a person enters the room. When enabled, the daylighting feature prevents lights from turning ON when the room is adequately illuminated by natural light.
Cutsheets
Technology:
- Passive Infrared (PIR) and Ultrasonic (US)
Power Requirements:
- 120 to 347 VAC, 50/60 Hz - Neutral Required
- 120 VAC:
- Incandescent/Tungsten - 0 to 800W, 50/60 Hz
- Fluorescent/Ballast - 0 to 1200W, 50/60 Hz
- Electronic Ballast (LED) 3A
- Motor Load: ¼ HP @ 125 VAC
- 230 VAC:
- Fluorescent/Ballast - 0 to 1200W, 50/60 Hz
- Electronic Ballast (LED) 3A
- 277 VAC:
- Fluorescent/Ballast - 0 to 2700W, 50/60 Hz
- Electronic Ballast (LED) 3A
- 347 VAC:
- Fluorescent/Ballast - 0 to 1500W, 50/60 Hz
- Electronic Ballast (LED) 3A
- 120 VAC:
Time Delays:
- Self-adjustable, 15 seconds/test (10 minutes Auto), or Selectable 5, 15, 30 minutes
Coverage:
- 2000 sq. ft.
Light Level Sensing:
- 0 to 300 foot-candles
Operating Environment:
- Temperature: 32°F - 104°F (0°C - 40°C)
- Relative humidity: 20% to 90%, non-condensing
- For indoor use only
Housing:
- Durable, injection molded housing. Polycarbonate resin complies with UL 94V-0
- Size: 1.42”H x 4.5”W (36.068mm x 114.3mm)
- Mounting: Mounts directly to ceiling tile, to a 4” square box and round mud ring or to 4” octagon box
LED Indicators:
- Red LED for PIR detection; Green LED for Ultrasonic detection
Standards:
- FCC Compliant
- cULus Listed
- RoHS Compliant
- MicroSet self-adjusting time delay and sensitivity
- Built-in light level sensor
- Units available for control of single or two separate loads
- Products tested to NEMA WD 7 - 2011 Occupancy Motion Sensors Standard
- LED Rated