Ceiling Mount Occupancy Sensor, Dual Tech, Low Voltage
The Dual Technology sensor’s combination of Ultrasonic and Passive Infrared technologies offers the most complete sensing equipment available today. MicroSet self-adjusting
Dual Technology sensors drastically simplify and reduce a contractor’s installation and adjustment time period.
The MicroSet self-adjusting technology continuously monitors multiple sub-frequencies in the event that if a continuous Doppler shift occurs, such as those created by airflow from an air duct, the sensor will identify the noise as continuous and then block it out of view at a select sub-frequency. It will continue to monitor other sub-frequencies for human motion. This avoids false-activation, while still maintaining the high level of sensitivity that is necessary for sensing minor motion in a changing environment. Separate concurrent time delays for both Passive Infrared and Ultrasonic technologies avoid false activations or deactivations. In Automatic On Mode, the lights turn ON when a person enters the room. In Manual On Mode (-R model only), the lights are turned ON by activating a momentary switch (model # GMDS-*) that is connected to the sensor. When enabled, the daylighting feature (-R models only) prevents lights from turning ON when the room is adequately illuminated by natural light.
Cutsheets
Technology:
- Passive Infrared (PIR) and Ultrasonic (US)
Mechanical:
- Size: 1.42” H x 4.5” W (36.068mm x 114.3mm)
- Mounting: Mounts directly to ceiling tile, to a 4” square box and round mud ring or to 4” octagon box
Environment:
- Operating temperature: 32°F to 104°F (0°C to 40°C)
- Relative humidity operating: 20% to 90% non-condensing
- For indoor use only
- Housing: Durable, injection molded housing. Polycarbonate resin complies with UL 94V-0
Electrical:
- Power Requirements:
- Input:
- 10-30 VDC from Greengate Switchpack or system
- Maximum current needed is 25mA per sensor
- Output:
- Open collector output to switch up to ten Greengate Switchpacks
- BAS with Isolated Form C Relay in (-R) model
- Isolated Form C Relay Ratings: 1A 30 VDC/VAC
- Input:
Hardware Specifications:
- LED Indicators: Red LED for PIR detection; Green LED for Ultrasonic detection
Controls and Performance:
- Time delays: Self-adjustable, 15 seconds/test (10 minutes Auto), or Selectable 5, 15, 30 minutes, or Zero Time Delay
- Coverage: 500, 1000, and 2000 sq. ft.
- Light sensing level (-R Models): 0 to 300 foot candles
Standards/Ratings:
- cULus Listed - Energy Management Equipment (UL916)
- FCC Compliant
- RoHS Compliant
- MicroSet self-adjusting Time Delay and sensitivity
- Optional built-in light level sensor
- Optional BAS/HVAC isolated relay
- Products tested to NEMA WD 7 - 2011 Occupancy Motion Sensors Standard
- Selectable Walk-Through Mode
- Dual Relay control