LightLEEDer-24 -32 -40 -48 Microlite® Retrofit Insert Emergency UL 924 LightLEEDer-24 -32 -40 -48 Microlite® Retrofit Insert Emergency UL 924

LightLEEDer Retrofit Insert Emergency UL 924 (GE compatible)

Models: LLGERI-22-EM, LLGERI-30-EM, LLGERI-38-EM, LLGERI-46-EM

A LightLEEDer Retrofit Insert -22 -30 -38 -46 Emergency UL 924 can take your present outdated or failing lighting control system and get it up to today's standards.  The retrofit is compatible with lighting panels manufactured by GE. It provides a dependable, flexible, and energy savings controller featuring the robust Reliant40 relay.  The EM Retrofit provides Emergency UL 924 operation for the panel relays and meets NFPA  requirements. These panels will automatically provide a Force On, Force Off, or No Change operation for the relays based on loss of normal power. Under normal conditions, all the enhanced features of the LightLEEDer system are available with this retrofit system. Upgrades are as simple as removing the existing hardware and replacing it with the hardware  provided on a single backplate insert, reusing the existing enclosure, conduit, and wiring.  It is provided with a hinged locking flush mount door.

Cutsheets

LightLEEDer GE Retrofit Insert Emergency UL 924

Installation Guides

LightLEEDer GE Retrofit Insert Emergency UL 924 Installation Guide

Specifications

Relays: 

  • Superior latching relays 
  • Switch type override control 
  • Lockout feature disables control from panel 
  • 40 Amps @ 120, 277, 347 VAC 
  • SCCR to 18,000 symmetrical amps 

Safeguards: 

  • Power surge and spike suppression up to 123 volts on the 24VAC power input 
  • Data line surge and spike suppression up to 8kv direct and 15kv thru air 
  • Memory retention for firmware and programming up to 200 years and electrostatic discharge to 4kv 
  • Real-Time-Clock time retention 45 days or greater without power 
  • Internal memory backup and restore 

Physical: 

  • 22 Relay Insert: 17.25"H x 15.04" W x 4.25" D (22.5" H x 24" W Door Included) 
  • 30 Relay Insert: 20.18"H x 15.04" W x 4.25" D (22.5" H x 24" W Door Included) 
  • 38 Relay Insert: 28.18"H x 15.04" W x 4.25" D (36" H x 24" W Door Included) 
  • 46 Relay Insert: 28.18"H x 15.04" W x 4.25" D (36" H x 24" W Door Included) 
  • Double sided construction similar to GE® 
  • Provided with pre-drilled mounting holes 
  • High voltage barriers separate Normal/Emergency/Class2
  • Relay Bypass output module (RBOM) 
  • Phase monitering module (PMM) 
  • NOTE: If door size is not listed contact ILC 

Electrical: 

  • 120/277 VAC @ 1 amps  
  • PMM monitors 120/277VAC   

Capacities: 

  • Up to 46 single pole relays with PMM 
  • 1 to 4 add-on modules   

Operating Environment: 

  • Location: Interior space 
  • Operating Temperature: 0° to 50° C  
  • Humidity: 10% - 90% Non-condensing  
  • Atmosphere: Non-explosive/corrosive  
  • Vibration: Stationary 

Certifications and Approvals: 

  • UL and CUL listed 
  • FCC Part 15 
  • UL 924 
  • Title 24 
  • ASHRAE compliant 
  • LEED compliant 
Features
  • Made in the USA 
  • Digital CAT5 ready 
  • Electronics, Relays, and Transformer provided on a single insert 
  • UL 924 bypass relay operation of R40 relays 
  • Selectable Force On, Force Off, or No change 
  • Standard Relays R40-1 relay supported, Non-Addressable option supports 1, 2 and 3-pole R40 
  • Addressable relay driver boards provided as standard for Left/Right sequencing, non-addresable option provides Odd/Even sequencing 
  • Normal & EM relays in the same enclosure 
  • High Voltage Dividers for separation 
  • 3-Phase monitoring module (LL-PMM) 
  • Remote test switch input and status output 
  • NO/NC dry contact output from PMM 
  • Door Included for the enclosure  
  • Reuse existing enclosure 
  • LightLEEDer standard panel operation supported 
  • Network compatible with other LightLEEDer panels and BAS interfaces