Wall Switch Sensor, PIR, Low Voltage
The ONW-P-1001-SP is designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights on. These sensors have multi-segmented lenses. For units to sense motion, the person must cross between two segments. The distance between segments increases the farther you are from the sensor, so motion has to be larger the farther you are from the unit. PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-sight to the person making the motion. In Automatic On Mode, the lights turn ON when a person enters the room. In Manual On Mode, the lights are turned ON by pressing the universally recognized light icon pushbutton. The sensor includes self-adaptive technology that continuously self-adjusts sensitivity and time delay in real-time, maximizing the potential energy savings that are available in the particular application. The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding individuals to take control of their lighting to maximize energy savings. HVAC mode allows the load connected to the Form C BAS relay to remain on when the lights are turned OFF manually. Applications may include keeping the room at a desired temperature while giving a presentation and the lights are OFF.
Cutsheets
Technology:
- Passive Infrared (PIR)
Mechanical:
- Mounting Plate Dimensions: 4.195” H x 1.732” W (106.55mm x 44mm)
- Product Housing Dimensions: 2.618” H x 1.752” W x 1.9” D (66.5mm x 44.5mm x 48.26mm)
Environment:
- Operating temperature: 32°F to 104°F (0°C to 40°C)
- Relative humidity operating: 20% to 90% non-condensing
- For indoor use only
Housing:
- Durable, injection molded housing. ABS resin complies with UL 94V-0
- Mounting: Fits in a standard 3.5” deep back box. Can be mounted in multiple gang back box Refer to NEC box calculation for properly sized mounting box
Electrical:
- Input:
- 10-30 VDC from Greengate Switchpack or Greengate system
- Maximum current needed is 25mA per sensor
- Output:
- Open collector output can switch up to ten Greengate Switchpacks
Hardware Specifications:
- LED Indicators:
- Red LED = PIR detection
- Green LED = acts as EcoMeter or night light locator
Controls and Performance:
- Time delays: Self adjusting 15 seconds/test (10 min. Auto), Selectable 5, 15, 30 minutes
Isolated Form C Relay Ratings:
- 1A 30 VDC/VAC
Coverage:
- Major motion: 36’ x 30’
- Minor motion: 20’ x 16’
Light sensing level:
- 0 to 200 foot candles
Standards/Ratings:
- cULus Listed
- FCC Compliant
- RoHS Compliant
- Low voltage sensors utilize an isolated Form C relay that integrates directly with lighting control, building, and HVAC systems
- Low voltage switches do not require conduit in most markets thus lowering installation costs
- Selectable built-in light level sensor
- NEMA WD7 Guide robotic method utilized to verify coverage patterns
- Tracking/HVAC Mode